ABB AC 900F学习笔记119:Freelance_Engineering_Process_Stations-25

2021-09-04 13:31:33  阅读:151  来源: 互联网

标签:900F ABB 安全值 power Stations 800F AC values CPU


继续学习。

6.4 Power fail signal (PF) and power fail 电源故障信号和电源故障 I/O modules maintain the last values until they have recognized the connection interruption and then adopt safety values until the CPU module sends actual values after restart. In case of power failure of the I/O module, output levels adopt zero voltage and/or zero current. I/O模板识别出最后一次值直到它们识别出连接中断,然后采取安全值,直到CPU发送实际值后重新启动。当IO模块断电时,输出零电压和/或零电流。   After voltage returns, I/O modules only change their output level when the CPU module communicates actual values. 恢复电压后,当CPU模板通讯实际值时,I/O模板改变其输出值。   6.4.1Power fail signal (PF) and no power fail 电源故障信号(PF)和断电故障  
PF < 15 ms 电源故障时间 < 15ms While the power fail signal is active, the CPU module or the AC 800F controller does not communicate current values; I/O modules independently maintain the last values. 当电源故障信号激活,CPU模块或者AC 800F控制器无法通讯当前值;I/O模块 独立的保持前一次的数值。
PF > 15 ms 电源故障时间 > 15ms I/O modules maintain the last values until they have recognized the connection interruption to the CPU module or to the AC 800F controller before they adopt the configured safety values The safety value are maintained until the AC 800F controller has performed a warm start and provides the I/O modules with new values.  在采取设定的安全值之前,I/O模板保持最近的数值直到识别出与CPU模板或者 AC 800F控制器的连接中断。保持安全值直到AC 800F执行热启动,提供I/O 模板新的数值。  
  6.4.2Power fail signal (PF) and power fail 电源故障信号和电源故障 I/O modules maintain the last values until they have recognized the connection interruption and then adopt safety values until the CPU module or the AC 800F Controller provides them with the current values upon restart. In case of power failure of the I/O module, output levels adopt zero voltage and/or zero current. I/O模板保持最近的值直到识别出连接中断。然后采取安全值直到CPU模板或者AC 800F控制器重新启动,提供给它们最新的数值。当I/O模块断电时,输出零电流或者零电压。   When power is supplied again, the I/O modules change their output level only when the CPU module or the AC 800F controller communicates current values. This does not apply to the analog output modules. As long as there is no failure in the external power supply, they keep the last values. Only when the power supply of the AC 800F controller is ensured again, the outputs are de-energized. 当电源恢复,只有当CPU模块或者AC 800F模块通讯当前值时,I/O模块才会改变其输出数值。这不适用于模拟量输出模块,它们保持最近的数值。只有再次确认AC 800F控制器的电源供应时,输出断电。   6.4.3Safety values for field devices 现场设备安全值   The cyclic data exchange between the PROFIBUS master and the connected slaves is monitored. When the cyclic data exchange is interrupted, the safety values can be assumed. The output channels feature manufacturer-specific safety values. Depending on the process requirements, the safety values for input channels can be configured to "Hold the last value" or to a particular value/status. PROFIBUS主站和连接的从站之间的周期性数据交换被监控。当周期性数据交换中断,采取安全值。输出通道采取制造商分配的安全值。根据工艺需求,输入通道的安全值可以配置为“保持最后一次值”或者特定的值/状态。  
A possible power failure can be evaluated by means of a system variable and used in the user program. 可能的电源故障可以通过系统变量来评估,使用在用户程序中。

标签:900F,ABB,安全值,power,Stations,800F,AC,values,CPU
来源: https://www.cnblogs.com/fishingsriver/p/15226383.html

本站声明: 1. iCode9 技术分享网(下文简称本站)提供的所有内容,仅供技术学习、探讨和分享;
2. 关于本站的所有留言、评论、转载及引用,纯属内容发起人的个人观点,与本站观点和立场无关;
3. 关于本站的所有言论和文字,纯属内容发起人的个人观点,与本站观点和立场无关;
4. 本站文章均是网友提供,不完全保证技术分享内容的完整性、准确性、时效性、风险性和版权归属;如您发现该文章侵犯了您的权益,可联系我们第一时间进行删除;
5. 本站为非盈利性的个人网站,所有内容不会用来进行牟利,也不会利用任何形式的广告来间接获益,纯粹是为了广大技术爱好者提供技术内容和技术思想的分享性交流网站。

专注分享技术,共同学习,共同进步。侵权联系[81616952@qq.com]

Copyright (C)ICode9.com, All Rights Reserved.

ICode9版权所有